Investigation of thermal behaviour of a hybrid concrete floor using embedded sensors
Abstract
Concrete structures expand and contract in response to temperature changes which can result in structural strain and
cracking. However, there is a limited amount of robust field data on hybrid concrete floor structures. Shortage of such
data impacts on our understanding of how concrete structures respond to thermal effects and ultimately the overall
design of concrete structures. Thus, a comprehensive structural and environmental monitoring strategy was implemented
by the authors during the construction of an educational building. Sensors were embedded in the precast
and in situ components of a hybrid concrete lattice girder flat slab so that the thermal response of the floor during the
manufacture, construction and operational stages could be investigated. Many aspects of the thermal behaviour of
the floor during the construction phase were monitored using the embedded sensors. The early-age thermal effects
during curing and the impact of the variation of ambient temperature (daily and seasonal) and solar radiation on the
behaviour of concrete floor is explored in the paper. Values for restraint factors and the in situ restrained coefficient of
thermal expansion of concrete are calculated using the data from the embedded sensors. Numerical modelling of the
thermal behaviour of the hybrid concrete floor was undertaken and validated using the real-time field measurements.
The data presented and analysed in this paper can be used to improve the understanding and modelling of the
thermal behaviour of a hybrid concrete floor. This will assist with improved design of sustainable buildings as it allows
the environmental performance of the floor to be optimised with respect to controlling the internal environment,
thermal mass and energy efficiency.